Rev. 10/98 35 949-1239-3
SPECIFICATIONS
Selectable Inputs: Thermocouple, RTD, current or voltage.
Input Impedance:
Thermocouple = 3 megohms minimum. RTD current = 200 µA.
Current = 249 ohms. Voltage = 5000 ohms.
Set Point Range: Selectable.
Displays: Two 4 digit, 7 segment 0.3" high LEDs. PV red, SV green.
Control Action: Reverse (usually heating), Direct (usually cooling) select-
able for single or dual set point models.
Proportional Band: 6 to 5000 °F or equivalent °C for temperature inputs.
6 to 9990 counts for current or voltage inputs.
Reset Time (Integral): Off or 0.1 to 99.9 minutes.
Rate Time (Derivative): Off or 0.01 to 99.99 minutes.
Cycle Rate: 2 to 80 seconds,
Approach Rate: Off to 99.99 minutes.
On - Off Differential: Adjustable 1° F to full scale in 1° steps (equivalent
°C), or 1 count to full scale in 1 count steps for current and voltage
inputs.
Alarm On - Off Differential: 2° F or equivalent in °C, or 2 counts.
Accuracy: ±0.25% of span, ±1 least significant digit.
Resolution: 1 degree, 0.1 degree, or 1 count.
Line Voltage Stability: ±0.05% over the supply voltage range.
Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)
maximum.
Common Mode Rejection: 140 db minimum at 60 Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
Isolation: Relay and SSR outputs are isolated. Current, voltage, and logic
outputs must not share common grounds with the input.
Supply Voltage: 100 to 240 VAC, nom., +10 -15%, 50 to 400 Hz. single
phase; 132 to 240 VDC, nom., +10 -20%. This applies to the instru-
ment power only.
Power Consumption: 5VA maximum.
Operating Temperature: -10 to +55 °C (+14 to 131 °F).
Storage Temperature: -40 to +80 °C (-40 to 176 °F).
Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at
55 °C non-condensing.
Memory Backup: Non-volatile memory. No batteries required.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dwyer Instruments Love Controls 1600 Series and is the answer not in the manual?

Dwyer Instruments Love Controls 1600 Series Specifications

General IconGeneral
BrandDwyer Instruments
ModelLove Controls 1600 Series
CategoryControl Unit
LanguageEnglish

Related product manuals