949-1239-3 36 Rev. 10/98
Control Output Ratings:
1. SSR, 3.5 A @ 250 VAC at 25 °C. Derates to 1.25 A @ 55 °C.
2. Relay, Form A contact (SPST), 3 A @ 250 VAC resistive; 1.5 A @
250 VAC inductive; Pilot Duty Rating: 250 VA, 2 A @ 125 VAC or
1 A @ 250 VAC.
3. Alarm Relay, Form A contact (SPST). Same rating as control relay
(2) above.
4. Current ( non-isolated), 0 to 20 mA across 600 ohms maximum.
5. Voltage (non-isolated), 0 to 10 VDC across 500 ohms minimum.
6. Logic (non-isolated), 5 VDC @ 25 mA.
Panel Cutout: 45 mm x 45 mm (1.775" x 1.775").
Depth Behind Mounting Surface: 115.3 mm (4.54").
Weight: 227 g (8 oz).
Agency Approvals:
UL E83725, CSA LR40125.
Front Panel Rating: IP66, UL Type 4X.