ATC770 Microprocessor-Based Pressure/Process Controller 79
Range: Use and keys to switch the upper display from OFF to On 4, then press FUNC
key to load the default data of the parameters belonging to group 1, group 2, group
3 and group 4.
11.5 GROUP 5 PARAMETERS
PRESSURE INPUT SELECTION - Group 5
Available: Always.
Upper display: Type of pressure input selection.
Lower display: PI.TYP
Range: Str, 0-20, 4-20, 0-5, 0-10. Strain gage, 0-20 mA, 4-20 mA, 0-5V, 0-10V
Default value: Strain gage.
NOTE: Remember to make the proper selection of internal jumpers.
REMOTE SET POINT INPUT SELECTION - Group 5
Available: Only if remote set point input circuit is fitted.
Upper display: Type of remote set point input circuit is fitted.
Lower display: RI.TYP
Range: OFF, 0-20, 4-20, 0-10. Disabled, 0-20 mA, 4-20 mA, 0-10V.
Default value: 4-20 mA.
NOTE: Remember to make the proper selection of internal jumpers.
CONTROL OUTPUT SELECTION - Group 5
Available: Always.
Upper display: Type of control output selection.
Lower display: CO.TYP
Range: 0-20, 4-20, 0-10, -10-10, 0-5. 0-20 mA, 4-20 mA, 0-10V, -10-10V, 0-5V
Default value: 0-10V.
NOTE: Remember to make the proper selection of internal jumpers.
RETRANSMISSION OUTPUT SELECTION - Group 5
Available: Only if retransmission output circuit is fitted.
Upper display: Type of retransmission output selection.
Lower display: OFF, 0-20, 4-20, 0-10, -10-10, 0-5. Disabled, 0-20 mA, 4-20 mA, 0-10V, -10-10V,
0-5V.
Default value: 0-10V.
NOTE: Remember to make the proper selection of internal jumpers.