EasyManua.ls Logo

E-Mon Class 3400 Meter - Page 9

E-Mon Class 3400 Meter
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CLASS 3400 METER
9 62-0391-03
3.0 METER TECHNICAL SPECIFICATIONS
(CONTINUED)
Input Voltage
Configuration
3-wire (Delta) Or 4-wire (Wye)
Mains Voltage Input Up To 600 VAC RMS Available
Input Power 6 VA Maximum Rating
Current Sensor
Rating
Up To 3200 Amps RMS AC Available
Power Factor 0.5 Leading Or Lagging
Line Frequency 50-60 Hz
Metering Accuracy ANSI C12.20
Voltage Operating
Range
+/-10% Of Rated Load
Temperature Range -20 C To +50 C (Standard indoor enclosure):
Relative Humidity
Range
0-95% Non-condensing
Altitude 2000 Meters Maximum
Voltage Overload +25% Continuously: +100% For 20 Cycles
Current Sensor
Overload
100% For 1 Minute Without Damaging Meter
Pollution Degree Degree 2 In Accordance With IEC 664
Installation
(Overvoltage)
Category
Category III
Measurement
Category
Category III
Enclosure Material UL Type 1 JIC Steel or Type 4X Plastic Rain Tight
Display Readout 4-line LCD
Standard Ranges 2-Wire Delta 120 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 120/208 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 120/240 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 277/480 VAC: 100, 200, 400, 800,1600, 3200 Amp
2-Wire Wye 277 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 400 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 480 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 600 VAC: 100, 200, 400, 800,1600, 3200 Amp
Modem Interface Cable: UL-listed/rated telephone cord, 4-
conductor, 300 VAC, stranded
conductors 22-26 AWG.
Cable Connector: RJ-11 IDC termination
Ckt Input Isolation 5.3K VAC
Baud Rate: 9600