Charger and AC transfer
Eaton 1250W / 1500W / 1800W Inverter Operation and Installation Guide IM SP180164 / Rev D www.eaton.com
Charger and AC transfer
AC input surge protection
175 J MOV is connected across the Line and Neutral of AC Input
Charger DC output over voltage shutdown
Battery over voltage protection: 16.0 +/- 0.5Vdc (Error code: E10)
Audio Aaarm: Beep @ 1 Hz and AC charger is latched off
Bypass mode is available
To reset error code, remove AC Input and turn unit off and on
Dead battery charging
Battery voltage must meet the following conditions or Error code E11 will display:
Initial battery voltage must be 10V or higher for charge to commence
In event battery voltage drops below 10V after charge is initiated (added load) maximum time for battery voltage to rise
above 10V in Bulk charge: 15 minutes
Audio alarm: Beep @ 1 Hz and AC charger is latched off following 15 minute delay
Bypass mode is available
To reset error code, remove AC Input and cycle unit off and on until reset