Matrix Telecom Inverter System
Installation and Operation Guide
Issue:
IPN 997-00012-68D
Issue Date:
February 2010
Eaton Corporation
Telecommunications Power Solutions
www.eaton.com/telecompower
DCinfo@eaton.com

Table of Contents

Questions and Answers

  • R
    Robin MccormickAug 18, 2025
    What to do if my Eaton INV-4815E Inverter has no AC output and all LEDs are off?
    • M
      Mr. Anthony LittleAug 18, 2025
      First, check if all input cables are firmly connected to the power source and that the power source is switched on and has sufficient power. Also, verify that all inserted inverter modules are the same model.
  • K
    Katie GoodAug 20, 2025
    Why is the red LED on my Eaton INV-4815E on and there is no AC output?
    • O
      Oscar NealAug 20, 2025
      The red LED and lack of AC output could indicate several issues. Check that the input wiring has correct polarity (positive to positive, negative to negative). Ensure the output voltage is within the operating range of your connected device. Also, verify that the inverter output is not shorted by turning off the input power source to remove any short circuits. Finally, negative power protection could be the cause. For multi-shelf systems, remove any jumper on the JP2 connector. For single-shelf systems, ensure there is a jumper on the JP2 connector.
  • E
    Eric AshleyAug 23, 2025
    What to do if my Eaton INV-4815E has no AC output and both yellow and red LEDs are on?
    • A
      Allen WaltersAug 23, 2025
      This usually means the load exceeds 125% of the inverter's capacity. Reduce the load to below 100% of the total power rating.
  • L
    leoncarlosAug 26, 2025
    What does it mean if the red LED is flashing fast on my Eaton Inverter?
    • R
      Ralph MarshallAug 26, 2025
      A rapidly flashing red LED can indicate that the inverter failed to soft start or that the inverter temperature is above the limit. Try rebooting the inverter system by switching the input power source off and on. If that doesn't work, let the inverter idle to cool down for a few minutes.
  • Q
    qgrayAug 28, 2025
    What does it mean if the yellow LED is on while AC output exists on my Eaton INV-4815E?
    • B
      Brett SpearsAug 28, 2025
      If the yellow LED is illuminated while AC output is present, it signifies that the load is over 100% but below 125% of its total power rating. Reduce the load to below 100%.
  • T
    Taylor RyanAug 30, 2025
    Why is the yellow LED flashing on my Eaton INV-4815E Inverter when AC output exists?
    • O
      obrienbrittanyAug 31, 2025
      A flashing yellow LED during AC output suggests that the input voltage is outside the operating range. Make sure the input voltage is between 45V and 58V, and check the connection to the battery or DC source.
  • N
    Nichole JenkinsSep 2, 2025
    What does it mean when the Eaton Inverter continuously delivers power, but the red LED is flashing slowly?
    • R
      Ronald JonesSep 2, 2025
      A slowly flashing red LED while the inverter is delivering power can point to an EEPROM failure or a fan failure. Try rebooting the inverter system by switching the input power source off and on. If the fan is blocked, clear the obstruction. If the fan is not working, the inverter may require servicing.
  • S
    Samuel Perkins DVMSep 4, 2025
    How to troubleshoot an Eaton INV-4815E module that cannot be properly inserted?
    • C
      cynthia19Sep 4, 2025
      Ensure that you are not trying to insert an STS module into the inverter shelf, as the inverter shelf only holds inverter modules. Also, verify that the inverter module is the correct model. All inverters must be the same model.
  • A
    amyjohnsonSep 7, 2025
    What does it mean if the yellow LED is on and there is no AC output from my Eaton INV-4815E?
    • J
      Jason MosleySep 7, 2025
      The absence of AC output with a lit yellow LED indicates that both the inverter and the utility AC source are in an abnormal state. Check both the AC mains and the inverter output.
  • R
    Ricky GilbertSep 9, 2025
    What does it mean if the green LED is on and the red LED flashes at 1Hz on my Eaton Inverter, while the AC output is normal?
    • R
      Rebecca BauerSep 9, 2025
      This indicates an EEPROM fault, meaning the EEPROM cannot correctly write or read data, or a CAN communication error. Check the connection of CAN signal cables. The EEPROM fault will not influence the STS AC output and the alert will turn off automatically after 10 seconds.

Summary

General Description

Matrix Inverter System

Describes the core product, its integrated AC power system, and its capabilities.

Preparation

Battery Precautions

Outlines critical safety measures for handling, charging, and disposing of batteries.

Installation

Frame Assembly

Describes the steps for assembling the inverter chassis and other system frames.

Wiring Connection

Covers the procedures for connecting system wiring, including wire size considerations.

Module Installation and Removal

Explains the procedures for installing and removing STS and inverter modules.

Operation

Pre-Operation Check

Lists essential checks required before applying power to the system.

Apply Power

Details the step-by-step procedure for applying power to the system.

Status Monitoring

Explains how to monitor system status using the controller's LCD screen.

Parameter Setting

Guides on configuring system parameters, including password protection.

Parameter Programming

Outlines how to program various inverter and STS module parameters.

Maintenance

Preventative Maintenance

Provides routine maintenance schedules and recommendations for optimal performance.

Troubleshooting

Offers guidance for resolving system issues, errors, and LED status interpretation.

Specifications

STS;MBS Operation

MBS Switch Positions

Describes the five positions of the Maintenance Bypass Switch (MBS) and their functions.

Default Values

Controller Menus

Worldwide Support

Eaton INV-4815E Specifications

General IconGeneral
ModelINV-4815E
Output Power1500W
Input Voltage48V DC
Battery TypeLead Acid
Operating Temperature0°C to 40°C