Why does my Eaton 150 VCP-T16 Other circuit breaker keep opening?
- AAustin VaughanAug 9, 2025
If your Eaton Other circuit breaker undesirably opens, it could be due to several reasons: * The undervoltage release may be operating because the voltage is too low or zero. In this case, check and correct the UVR supply voltage to be within 85-110% of the rated voltage. * The shunt trip might be operating. Inspect the control signal(s) to the shunt trip and correct if necessary. * The trip latch could be defective. Inspect the latch condition and engagement before closing.