Step 9.
Install compression connector
ote:N Refer to the chart supplied with the crimp
connector for tool and die to be used.
Wire brush conductor (aluminum only).
Remove protective cap from compression connector.
Insert conductor completely into compression connector
and rotate connector to distribute inhibitor.
ote:N Connector must be fully seated on cable conductor.
Align flats of connector and apparatus bushing for
minimum conductor strain.
Make first crimp 1/2" (13 mm) below shoulder of
compression connector. (Refer to Figure 22).
Rotate each successive crimp 90° on compression
connector and allow 1/8" (3 mm) between crimps.
Wipe excess inhibitor from connector and adapter
surfaces.
Step 10.
Check di men sions
Check length from end of com pres sion con nec tor to top
of cable adapter.
Length should be be tween 6.50-7.25" (165 - 184 mm). (Re-
fer to Fig ure 23.)
Figure 23. Line illustration for dimensional check.
6.50-7.25"
(165-184 mm)
Cable
Adapter
Concentric
Neutral Wires
Tape
Marker
Compression
Connector
Figure 22. Line illustration of crimping area.
Bushing
ShoulderTool
Crimping
Area
Cable
Adapter
10
600 A 15/25 kV class BOL-T connector assembly installation instructions for MN650005EN February 2015