EasyManua.ls Logo

Eaton 600 A 15 kV class - Installation of BOL -T Connector Onto Apparatus Bushing

Eaton 600 A 15 kV class
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Install BOL-T T-body with mating parts
Step 11.
Install DT625 T-body
Clean and lubricate outside of cable adapter with lubricant
supplied.
Clean and lubricate inside of T-body with lubricant
supplied.
ote:N If test point T-body is used, insure test point is
opposite front plate side of T-body.
Without moving the cable adapter, slide T-body onto cable
adapter until compression connector eye is centered in
600 A interfaces. (Refer to Figure 24.)
ote:N The end of the cable adapter must line up with
the top edge of the tape marker after T-body
assembly. Refer to Figure 21.
Remove tape marker from cable.
Go to Step 12, page 12 to complete T-body termination.
Figure 24. Line illustration of BOL-T T-body installation.
T-body
Cable Adapter
Tape Marker
Concentric Neutral Wires
Lubricate
600 A Interfaces
Apparatus
Bushing
Test Point on
Accessible
Side
11
600 A 15/25 kV class BOL-T connector assembly installation instructions MN650005EN February 2015

Other manuals for Eaton 600 A 15 kV class

Related product manuals