EasyManua.ls Logo

Eaton 600 A 15 kV class - Compression Connector Procedure

Eaton 600 A 15 kV class
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Compression connector installation procedures
Equipment provided
BOL-T Connector Assembly Kit including:
T-body
Cable Adapter
Insulating Plug with Cap
Compression Connector with
11
/
16
" unthreaded spade
Silicone Lubricant
Threaded Stud
Instruction Sheets
Tools required
Torque Wrench and 1" socket for BOL-T
5/16" Hex Wrench for Separable Splice Applications
Cable Stripping Tools
Cable preparation
Step 1
Train cable
Position cable vertically so that it is centered between
apparatus bushing and parking pocket, parallel to, and 6"
(152 mm) from apparatus frontplate.
Provide adequate cable slack for cable movement
between standoff bushing and apparatus bushing.
Support cable as needed to maintain position.
Cut cable 1.75" (44 mm) from centerline of bushing. Refer
to Figure 14.
Figure 14. Line illustration for cable training.
Existing
Bushing
Cable
1.75" ± .25"
(44 mm ± 6 mm)
6"
(152 mm)
Table 3. Conductor Size and Type
Compression Connector
Concentric or
Compressed Compact or Solid
Compression
Conductor Code
AWG or
kcmil mm
2
AWG or
kcmil mm
2
No Connector 00
#2 35 1 - 11
#1 - 1/0 50 12
1/0 50 2/0 70 13
2/0 70 3/0 - 14
3/0 - 4/0 95 15
4/0 95 250 120 16
250 120 300 - 17
300 - 350 - 18
350 - 400 185 19
400 185 450 - 20
450 - 500 240 21
7
600 A 15/25 kV class BOL-T connector assembly installation instructions MN650005EN February 2015

Other manuals for Eaton 600 A 15 kV class

Related product manuals