Figure 32. Installing to connecting plugs.
In su lat ing Plug
Connecting Plug
Connecting Plug
Connecting Plug
Drain
Wire
Drain
Wire
5/16" Hex
Shaft
1" Wrench
Torque
Wrench
Socket
Wrench
Figure 33. Last insulating plug installation.
In su lat ing Plug
Insulating
Plug
Torque
Wrench
Connecting Plug
Drain
Wire
Drain
Wire
Repeat the previous assembly procedures for each
additional splice tap. (Refer to Figure 32.)
After the last connecting plug and T-body are installed,
obtain the second insulating plug. If stud has not
been factory installed, hand thread a 5/8" stud into the
insulating plug.
Install the second insulating plug, with stud, into the
open interface of the last T-body. Hand thread the
insulating plug into the connecting plug.
Secure the first insulating plug using a 1" wrench. Using
a 1" socket on a torque wrench, tighten the second
insulating plug to 55 ft-lbs. (Refer to Figure 33.)
Clean and lubricate the inner surface of two insulating
plug caps with the lubricant supplied.
Push the caps onto the insulating plugs until they snap
into place.
Connect one drain wire to the tie-off tab of each T-body
and connect the other end to a common ground point.
ote:N If splice is disassembled, all connecting plugs and
insulating plugs should be completely removed,
cleaned, regreased, and reassembled following
the above procedure to ensure connection points
are properly torqued.