EasyManua.ls Logo

Eaton 600 A 15 kV class - Page 12

Eaton 600 A 15 kV class
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Step 2.
Remove concentric neutral wires or jacket
ote: N Care should be taken to not cut or score the
neutral conductors when cutting the cable jacket.
Measure 12 3/4” (324 mm) from the end of cable. Refer
to Figure 18.
For jacketed neutral cable, remove the jacket to 12 3/4”
dimension.
For unjacketed neutral cable, bind neutral wires using
three (3) wraps of tape at 12 3/4” dimension.
Pull back concentric neutral wires. Allow enough extra
concentric neutral wires to connect to ground after installation
and allow movement to the insulated standoff bushing.
Step 3.
Remove insulation shield
Remove insulation shield length 9 3/4” (248 mm) from
the end of cable. Refer to Figure 19.
Do not cut or nick insulation.
Step 4.
Put tape marker in place
Measure 1” (25 mm) from the end of insulation shield.
Refer toFigure 19
Wrap two turns of tape to serve as marker for the cable
adapter location.
Step 5.
Remove conductor insulation
ote: N Do not pencil cable.
Remove insulation exposing bare conductor to a length of
4 3/8” (111 mm). Refer to Figure 17.
ote: N Do not unwind conductor strands.
Step 6.
Bevel insulation
Remove the sharp edge of insulation by beveling at a 45°
angle for approximately 1/4” (6 mm). Refer to Figure 18.
Figure 17. Line illustration of bare conductor length.
4 3/8" ± 1/8"
(111 mm ± 3 mm)
Tape marker
Bare conductor
Insulation
Figure 18. Line illustration of removing concentric neu-
tral wires.
Bevel
Insulation
1/4"
(6 mm)
Figure 19. Line illustration of cable stripback.
Bushing
Cable
1 3/4” ± 1/4”
(44 mm ± 6 mm)
12 3/4” ± 1/4”
(324 mm ± 6 mm)
Concentric neutral
wires
Figure 18. Line illustration of insulation bevel.
9 3/4"
(248 mm ± 3 mm)
1"
(25 mm)
Tape Marker
Insulation Shield
Insulation
8
600 A 15 kV and 25 kV class BT-TAP connector system installation instructions MN650004EN May 2021
Catalog data MN650004EN
Effective May 2021
Deadbreak apparatus connectors

Other manuals for Eaton 600 A 15 kV class

Related product manuals