-24- 
information about the mains power, the battery level, the UPS output 
and  the  load  level  could  be  displayed.  The  “STbY”  string  indicates 
UPS working in the No output mode.   
     
 
■ Figure 6.4 The No output mode 
6.6 ECO mode (Economy mode) 
It is also called high efficiency mode. After turning UPS on in ECO mode, 
the output power will be supplied from mains power directly via internal 
filter  while  the  mains  power  is  in  certain  range,  so  the  high  efficiency 
performance would be gained in ECO mode. Once the mains power is 
loss or out of range, the UPS will transfer to battery mode and the load 
will be supplied continuously by the battery.   
1)  ECO mode can be enabled through the LCD setting or the software 
(Winpower, etc.). 
2)    The transfer time of UPS output from ECO mode to battery mode is 
less than 10ms. It is suggested that takes account of application for 
some sensitive load. 
6.5 CVCF mode 
CVCF  (Constant  Voltage  Constant  Frequency)  which  is  also  called 
converter  mode,  UPS  would  works  in  frequency  free-run  with  fixed 
output frequency (50Hz or 60Hz). Once the mains are loss or abnormal, 
the  UPS  would  transfer  to  battery  mode  and  the  load  is  supplied 
continuously by the battery. 
1)    CVCF  mode  can  be  enabled  through  the  LCD  setting  or  the 
software (Winpower, etc.). 
2)    The normal power rating will be derating to 60% in converter mode.