5.1 Parallel UPS installation
In the parallel system, the installation of the UPS modular is the same as single UPS.
Please refer to Chapter 3.
Note:
If you configured a '1+1 parallel MBP' modular of this series, it need to be placed to
top layer of the parallel system for rack mounted; or left side for tower installed.
This is for a better cable-connection(as shown below):
Rack mount for parallel system Tower mount for parallel system
5.2 wiring
Cable-select table for the parallel system AC IN and AC OUT :
Parallel system
installed by 15KVA UPS (conductor cross-section, unit: mm²)
UPS
number
Mode
Main input
Bypass input
Ground wire
Output
Battery wire
Battery ground
L wire
N wire
L wire
N wire
L wire
N wire
Ground
2 UPS
3-1 16
16
50 50 50
50
50
50
25
25
3-3 16
16
10 10 16
10
10
10
25
25
1-1 95
95
50 50 95
50
50
50
25
25
1:3 95
95
10 10 95
10
10
10
25
25