3.3 Mechanical installation
1. This series support two installation modes: Tower installation and rack
installation.
2. To keep good ventilation, please keep a free-space (500mm at least) for front
/ rear panels of the module.
3. Do not carry the front/rear panel of the module during installing.
3.3.1 UPS modular installation
• Rack mount:
The UPS is suitable for installation in a 19-inch standard rack cabinet. It is
recommended that the depth of the cabinet be no less than 800mm.
1.
Install the rail kit(This is an optional configured). This rail kit is '2U & with
screw holes (M5)', the depth of the rail kit is: 415-763mm.
Fasten the rail kit to the cabinet with 8pcs M5 screws + washers (as
below):