84
Mode 3-3(single source)
1. Input: connect mian-ground cable (PE) to chassis first;
short ‘UPS input terminal N/N’ with ‘busbar #1’, then connect AC cable(N);
connect ‘UPS input terminal L1/L2/L3’ with AC cable(L1/L2/L3) and
‘jumper cable’ by back to back mounted;
then fix ‘jumper cable’ to ‘UPS bypass terminal L1/L2/L3’.
2. Output: connect ground cable (PE) to chassis first;
short ‘UPS output terminal N/N’ with ‘busbar #1’, then connect AC
cable(N);
connect ‘UPS output terminal L1/L2/L3’ to AC cable(L1/L2/L3).