IB01602015E For more information visit: www.eaton.com
Instruction Booklet
Effective: August 2010 Page 9
ATC-300 2-Postion Contactor
Based Transfer Switch
3.5 Features
A variety of standard and optional features are available for Eaton
ATSs. All features or combinations of features may not be avail
-
able on specific ATSs. All features and/or accessories are Under-
writers Laboratories (UL) listed unless noted.
3.5.1 Standard Features
The following is a list of the standard features for the ATC-300
Controlled ATS.
1. Time Delay Normal to Emergency (TDNE)
This feature provides a time delay when transferring from
the Source 1 to the Source 2 power source. Timing begins
when Source 2 becomes available. It permits controlled
transfer of the load circuit to Source 2.
Adjustable 0 - 1800 Seconds
2. Time Delay on Engine Starting (TDES)
This feature provides a time delay of the signal to initiate
the engine/generator start cycle in order to override
momentary power outages or voltage fluctuations of
Source 1.
Adjustable 0 - 120 Seconds
3. Time Delay Emergency to Normal (TDEN)
This feature provides a time delay of the re-transfer opera-
tion to permit stabilization of Source 1. Timing begins
when Source 1 becomes available. If Source 2 fails during
timing, then re-transfer is immediate overriding the time
delay.
Adjustable 0 - 1800 Seconds
4. Time Delay for Engine Cool-down (TDEC)
This feature provides a time delay of the signal to initiate
the engine/generator stop cycle after the re-transfer opera
-
tion. This allows the engine/generator to cool down by run-
ning unloaded. Timing begins on completion of the re-
transfer cycle.
Adjustable 0 - 1800 Seconds
5. Source 2 Monitoring and Protection
This feature provides monitoring and protection based on
the Source 2 voltage and/or frequency setpoints. All fea
-
ture 5 functions are Failsafe operations.
5B. 1-Phase Undervoltage and Underfrequency Protection
Adjustable Undervoltage:
Dropout: 78 - 97% of nominal
Pickup: (Dropout +2%) to 99% of nominal
Adjustable Underfrequency:
Dropout: 90 - 97% of nominal
Pickup: (Dropout +1Hz) to 99% of nominal
5C. 1-Phase Overvoltage/Overfrequency
Adjustable Overvoltage:
Dropout: 105 - 110% of nominal
Pickup: 103% to (Dropout –2%) of nominal
Adjustable Overfrequency:
Dropout: 103 - 105% of nominal
Pickup:101% to (Dropout -1Hz) of nominal
5D. 1-Phase Undervoltage
Adjustable Undervoltage:
Dropout: 78 - 97% of nominal
Pickup: (Dropout +2%) to 99% of nominal
5E. 1-Phase Overvoltage
Adjustable Overvoltage:
Dropout: 105 - 110% of nominal
Pickup: 103% to (Dropout –2%) of nominal
5F. 3-Phase Undervoltage
Adjustable Undervoltage:
Dropout: 78 - 97% of nominal
Pickup: (Dropout +2%) to 99% of nominal
5G. 3-Phase Overvoltage
Adjustable Overvoltage:
Dropout: 105 - 110% of nominal
Pickup: 103% to (Dropout –2%) of nominal
5H. Phase Reversal
For a 3-phase wye source, this feature monitors the phase
sequence of the sources. If a source does not have the
same ABC or CBA sequence as the setpoint value, that
source will be considered “Unavailable.
For a 3-phase delta source, this feature should be turned off
via the PHASE REV setpoint.
5J. All Phase Undervoltage and Underfrequency Protection
Adjustable Undervoltage:
Dropout: 78 - 97% of nominal
Pickup: (Dropout +2%) to 99% of nominal
Adjustable Underfrequency:
Dropout: 90 - 97% of nominal
Pickup: (Dropout +1Hz) to 99% of nominal
5K. All Phase Overvoltage/Overfrequency
Adjustable Overvoltage:
Dropout: 105 - 110% of nominal
Pickup: 103% to (Dropout –2%) of nominal
Adjustable Overfrequency:
Dropout: 103 - 105% of nominal
Pickup: 101% to (Dropout -1Hz) of nominal