ATC-900 Magnum Tranfer Switch O & M Manual
4.6 Voltage Selection Adjustment (Non-Connector)
Certain devices, such as the voltage selection panel, sensing 
relays, and timers need to be set and/or calibrated prior to placing 
the transfer switch equipment into service.  Adjustments for logic 
devices are described in the separate instructional document dedi-
cated to the specific logic being used.  Voltage selection adjust-
ments are described here. For newer switches (Nov 2014) there is 
a voltage selection connector.  Please see section 3.3.1 for the 
voltage selection types. If the voltage selection is not on the front 
of the transformer using a connector, then one would need to 
open the transformer and move the physical tap connectors.  The 
following is how to change the taps. 
Voltage selection is made at the multi-tap transformer subassem-
bly (see Figures 22, 22A, and 22B) mounted in the lower compart-
ment of the transfer switch. This subassembly includes two 
identical control power transformers with one connected to 
Source 1(NT1) and the other connected to Source 2 (ET1).  The 
control power transformers are mounted behind a removable panel 
(see Figure 22B).
Figure 22.Transformer and Taps.
Figure 22A.
Figure 22B.
• Remove the transformer pack cover by loosening the 4 screws 
located at each corner of the transformer pack assembly.
• The transformers are factory set on the voltage tap specified by 
the customer.  (See illustration above for location of various 
taps and voltages)
• Detach the spade connector from the existing voltage tap and 
place on the tap that is suitable for your application.
.
• After changing the taps on both transformers, replace the trans-
former pack cover and tighten all four screws.
PRIMARY
TERMINALS
SECONDARY
TERMINALS
415V   6
380V   5
240V   4
220V   3
208V   2
  0V   1
50/60Hz
12
11
10
9
SECONDARY 1
120V, 300VA
INTERMITTENT 50%
DUTY CYCLE
SECONDARY 2
120V, 25VA
7
9
10
11
12
   120V, 25A
12
11
9
10
120V 300VA
TOP: 7-480V 5-380V  3-220V  1-COMMON 
BOTTOM: 8-600V 6-415V  4-240V  2-208V
5
3
8
6
4
480V   7
600V   8
1
2
1268C19G07
Primary Side Connections:
Connection 1 - Tap on #1 Common
Connection 2 - Tap on the nominal 
system voltage 
 WARNING
DISCONNECT ALL SOURCES OF POWER OR DISCONNECT P7/S7
PRIOR TO PERFORMING THE FOLLOWING. FAILURE TO DO SO MAY
CAUSE SERIOUS INJURY OR DEATH.
 CAUTION
BE SURE THAT THE CORRECT VOLTAGE IS SELECTED TO MATCH
THE SYSTEM VOLTAGE. AN IMPROPER SELECTION AND/OR CON-
NECTION COULD RESULT IN EQUIPMENT DAMAGE.