6. Maintenance
6.1 Troubleshooting
Operation status Possible cause Action
Overload
Power requirement exceeds the
ATS capacity (greater than 105 % of
nominal).
Removesomeoftheequipment
from the ATS.The ATS continues
tooperate,butmayshutdown
if the load increases.The alarm
resetswhentheconditionbecomes
inactive.
Short-circuitfault
Ashort-circuitoccurred. Checkdeviceconnectionor
integrity.
Iferrorpersists,notethealarm
message and the ATS serial
number,andthencontactyour
service representative.
Internalrelayfault
Internalrelayfault,notethatthe
load is no powered.
Note the alarm message and the
ATSserialnumber,andthencontact
your service representative.
Source 1 or Source 2 power
supply fault
Internalpowersupplyofoneofthe
sourceisfaulty;theothersourceis
powering the load.
Note the alarm message and the
ATSserialnumber,andthencontact
your service representative.
EEPROMfault
EEPROMfault,notethattheloadis
still powered.
Note the alarm message and the
ATSserialnumber,andthencontact
your service representative.