Page 6
EATS16_EN
2. Presentation
2.4.2 Measures
Output current
(default display)
Output voltage
Input voltage : S1
(default display only when S1 voltage is out of tolerance)
Input frequency: S1
(default display only when S1 frequency is out of tolerance)
Input voltage : S2
(default display only when S2 voltage is out of tolerance)
Input frequency: S2
(default display only when S2 frequency is out of tolerance)
S1 and S2 phase shift
(availableonlywhenS1andS2arenotsynchronized)
2.5 ATS settings
OUTPUT: Sets voltage thresholds
-
200V-208V-220V-230 V (default)-240V
ALARM:Silentsalarm
-
ON:normalbeepinwarningorfaultmode,bydefault
OFF:silent.
SENSITIVITY (mainly for LIA UPS):Sets
Sensitivity mode for input mains detection.
-
Std:NormalSensitivity,bydefault
Lo:LowSensitivity,forcompatibilitywithdistorted
waveform.
P SOURCE:Setstheprioritysource Sc.1:PriorityonSource1,bydefault
Sc.2:PriorityonSource2
TRANSFER: Std:noadditionalbreakevenifS1andS2arenot
synchronized,bydefault
Gap:additionalbreakduringtransferifS1andS2are
notsynchronized.