3
Installation Leaet IL04209006E
Eective July 2010
PROFIBUS Module for use with
Motor Insight, C440 and S611
EATON CORPORATION www.eaton.com
Approvals / Certications
Electrical / EMC
ESD Immunity +/- 8kV air, +/- 4kV contact
Radiated Immunity (IEC61000-4-3) 10V/m 80-1000 MHz, 80%
amplitude modulation @
1kHz
Fast Transient (IEC61000-4-4) +/- 2kV communications
Surge (IEC61000-4-5) +/- 2kV shield-to-ground
RF Conducted (IEC610000-4-6) 10V, 0.15 80MHz
Ingress Protection Code IP20
Radiated and Conducted Emissions EN55011 (CISPR 11) Class A
Agency Certifications UL
®
508
cUL
®
(CSA C22.2 No. 14)
CE (Low Voltage Directive)
PROFIBUS Certification
Module Electrical Requirements
Voltage Range 18 - 30 Vdc
Current Draw Approx. 30 mA
Notes
For use with Eaton UL Listed Power Supply Catalog Nos. PSS55A,
PSS55B, PSS55C, or PS160E.
Any UL Listed isolated power supply with a maximum of 30 Vdc
output may be used, provided that a UL Listed or Recognized Fuse
rated no more than 3A maximum be installed.
5pin 24 VDC Power, RS485 Connector


Related product manuals