Installation of terminal options
Eyebolt terminal (Terminal code - B)
1. Insert threaded end of the eyebolt terminal body into
the tapped center hole of the Companion II fuse and
torque the eyebolt terminal to 10-15 ft-lbs. (Figure 8.)
Figure 8. Eyebolt terminal.
1.57"
(40 mm)
Figure 5. Transformer-mounted Companion II fuse with
distribution cutout.
DIRECT
CONNECT
ARRESTER
CUTOUT FUSE
LINK IN FUSE-
HOLDER
TRANSFORMER
PRIMARY
BUSHING
Figure 6. Completely Self-Protected (CSP) transformer-
mounted Companion II fuse without separate
distribution cutout.
ARRESTER
COMPANION II
FUSE
TRANSFORMER
PRIMARY
BUSHING
Figure 7. Lightning-protected transformer (LPT)
installation.
COMPANION II
FUSE
TRANSFORMER
PRIMARY
BUSHING
DIRECT
CONNECT
ARRESTER
COMPANION II
FUSE
FUSE CUTOUT
WITH DUAL
ELEMENT FUSE
(X OR D LINK)
HIGH ENERGY
SECONDARY
ARRESTER
4
COMPANION II BACK-UP CURRENT-LIMITING FUSE INSTALLATION INSTRUCTIONS MN132009EN