TM293 MEDC DB3BM UL Technical Manual
SOUNDER/HORN – DB3BM UL TM293.A August 2022 www.eaton.com
7.0 SPECIAL CONDITIONS FOR SAFE USE
For replacement purposes M5 x 0.8 x 20 mm long
cover bolts shall be used and shall have a property
class of A2-70 or stronger. Reduced shank fasteners
must be used with covers employing threaded holes.
Fully threaded fasteners must be used with covers
employing plain clearance holes.
The flameproof joints are not intended to be repaired.
Potential Electrostatic Charging Hazard. If the unit
requires cleaning, only clean exterior with a damp cloth
to avoid electrostatic charge build-up. See instructions
for further guidance
If metal certification labels are attached to the horn
they are known to be capable of retaining the
following charges.
3.33pF - Label size 65mm x 40mm (2.5”x1.5”)
7.15pF Label size 105mm x 42.5mm (4” x 1.3/4”)