Page 20 I.L. 17562
PR 0.3 Effective 8/99
Table 4.1 Motor State (Default Mode) Display
Display Complete Help Message Description
READY--1 READY TO START MOTOR,
SINGLE PHASE TEST MODE
WARNING
MP-3000 has been set to 1 PHASE for bench
testing only. Will not protect a 3-phase
motor. Change setpoint P13L1 to 3 PHASE
for normal motor protection.
READY--3 READY TO START MOTOR,
THREE PHASE MODE
Motor is stopped and MP-3000 is ready for a
start, 3-phase mode.
RUN MOTOR IS RUNNING Motor is running, as indicated by phase
currents.
START ATTEMPTING TO START
MOTOR
Motor is starting, and has not yet reached
transition to RUN as defined by user settings
DISARMED WARNING RELAY IS
DISARMED AND CAN NOT TRIP
WARNING
Protection functions have been blocked from
operating the trip relay by user setting
P12L18. MOTOR IS UNPROTECTED. This
mode of operation is for commissioning in a
critical process only. See Section 5.12.18.
ABKSP XX ANTI-BACKSPIN ACTIVE,
REMAINING MINUTES ACTIVE
SHOWN
The motor is stopped, and the trip contact has
been opened to prevent restarting until the
antibackspin time delay has expired. XX is
the remaining minutes before restarting is
allowed.
ILLEGAL AN ILLEGAL REQUEST WAS
MADE
Response to request for an action which the
relay cannot perform.