Table 4.2 Monitor Mode Display
Page Line Complete Help Message Description
MONITOR MONITOR OF REAL TIME VALUES Monitor mode
MONT I REAL TIME DATA FROM CURRENT
MEASUREMENTS
Current monitoring data follows
IAVG XXX AVERAGE OF THREE PHASE CURRENT Average rms current of 3-phase
currents in amps
IA XXX PHASE A CURRENT IN AMPS Actual ac line motor rms current
IB XXX PHASE B CURRENT IN AMPS
IC XXX PHASE C CURRENT IN AMPS
IG XXX GROUND FAULT CURRENT IN AMPS Actual ground current
%IA XXX PHASE A CURRENT AS A PERCENT OF FULL
LOAD AMPS
The percents of the actual
%IB XXX PHASE B CURRENT AS A PERCENT OF FULL
LOAD AMPS
monitored current in amps
%IC XXX PHASE C CURRENT AS A PERCENT OF FULL
LOAD AMPS
%UB XXX PHASE UNBALANCE – IF POSITIVE THE RATIO
OF NEGATIVE TO POSITIVE SEQUENCE
CURRENT – IF NEGATIVE THE INVERSE
Ratio of negative sequence current to
positive sequence current in percent.
If a phase reversal exists, then the
ratio is inverted and a negative sign
is displayed.
MONT RTD REAL TIME DATA FROM RTD MODULE RTD monitoring data follows. Page
is only visible when an URTD is
communicating with the MP-3000
WT1 XXXX WINDING TEMP 1 IN DEGREES F (or) C RTD reading – terminals 1,2,3
WT2 XXXX WINDING TEMP 2 IN DEGREES F (or) C RTD reading – terminals 4,5,6
WT3 XXXX WINDING TEMP 3 IN DEGREES F (or) C RTD reading – terminals 7,8,9
WT4 XXXX WINDING TEMP 4 IN DEGREES F (or) C RTD reading – terminals 10,11,12
WT5 XXXX WINDING TEMP 5 IN DEGREES F (or) C RTD reading – terminals 13,14,15
WT6 XXXX WINDING TEMP 6 IN DEGREES F (or) C RTD reading – terminals 17,18,19
MT1 XXXX MOTOR BEARING TEMP 1 IN DEGREES F (or)
C
RTD reading – terminals 20,21,22
MT2 XXXX MOTOR BEARING TEMP 2 IN DEGREES F (or)
C
RTD reading – terminals 23,24,25
LT1 XXXX LOAD BEARING TEMP 1 IN DEGREES F (or) C RTD reading – terminals 26,27,28
LT2 XXXX LOAD BEARING TEMP 2 IN DEGREES F (or) C RTD reading – terminals 29,30,31
AXT XXXX AUXILIARY TEMP IN DEGREES F (or) C RTD reading – terminals 33,34,35
MONT MTR REAL TIME MOTOR DATA Motor monitoring data follows
VER XXXX SOFTWARE VERSION NUMBER MP-3000 software version in use
%I2T XXX PERCENT OF I2T TRIP LEVEL Percent of thermal bucket used