Page 22 I.L. 17562
PR 0.3 Effective 8/99
Page Line Complete Help Message Description
TUS XXX TIME IN MINUTES UNTIL NEXT START CAN
OCCUR
Displays largest amount of time in
minutes among three functions:
anti-backspin, starts per unit time,
and time between starts
RMST XX REMAINING STARTS Number of starts remaining if starts
per time is programmed
OST XXX TIME LEFT ON OLDEST START IN MINUTES Remaining time allowed on oldest
start for starts per time if
programmed. If motor start/time is
exceeded, this is time in minutes
before restart is permitted.
ICM XXXX ADDRESS ON THE IMPACC NETWORK IN
HEXADECIMAL
Address of device if on INCOM
communications network, only visible
if on the network
MONT TIM DATE AND TIME Current date and time with display
format as programmed
HH.MM XM
or
HH.MM
CURRENT TIME 12-hour format
or
24-hour format
MM/DD/YY
or
DD/MM/YY
CURRENT DATE Common format
or
European / military format