I.L. 17562
Page 23
PR 0.3 Effective 8/99
Table 4.3 View Settings Mode/Program Worksheet
Program Date __________ Control
Schematic_________________________________________
Unit ID / Starter Type _________________________ Work Order # _______________________
Motor HP __________ Mfgr. __________ Serial # ______________Volts___________________
FLA __________ LRC ___________ Stall Time/LRT ____________Accel Time
______________
SF ___________________RTD Type __________________ Other
________________________
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
Page 1 SP MOTOR SETPOINTS FOR MOTOR CONSTANTS
1 FLA XXXX FULL LOAD AMPS 10-3000 amps (1
amp.
increments)
10
2 LRC XXXX LOCKED ROTOR CURRENT
% OF FLA
300-1200 % (1
% increments)
300
3 LRT
XXX
MAXIMUM ALLOWABLE
STALL TIME IN SECONDS
1-120 sec. (1
sec. increments)
1
4 UTC XXX ULTIMATE TRIP CURRENT IN
% FLA
85-150% (1%
increments)
85
5 PCT XXXX PHASE CT RATIO
NUMERATOR IN PRIMARY
AMP
10-4000 A
(increments of 1)
10
6 GCT XXXX GROUND CT RATIO
NUMERATOR IN PRIMARY
AMP
10-4000 A
(increments of 1)
50
7 FREQ 50
or
FREQ 60
50 OR 60 HERTZ LINE
FREQUENCY
Toggles between
FREQ 50 and
FREQ 60
FREQ 60
8 REV
or
NON REV
REVERSING OR
NONREVERSING STARTER
Toggles between
REV and
NONREV
NONREV
Page 2 SP RTD SETPOINTS FOR RTD INPUTS
1 RTD IN C
or
RTD IN F
DISPLAYED IN DEGREES C
OR F
Toggles between
RTD IN C and
RTD IN F
RTD IN C
2 WD T XXX WINDING TEMP TRIP 0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
3 WD A XXX WINDING TEMP ALARM 0-199°C, OFF /
32-390°F, OFF
(1°increments)
80