Page 24 I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
4 MB T XXX MOTOR BEARING TRIP 0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
5 MB A XXX MOTOR BEARING ALARM 0-199°C, OFF /
32-390°F, OFF
(1°increments)
80
6 LB T XXX LOAD BEARING TRIP 0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
7 LB A XXX LOAD BEARING ALARM 0-199°C, OFF /
32-390°F, OFF
(1°increments)
80
8 AX T XXX AUXILIARY TRIP 0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
9 AX A XXX AUXILIARY ALARM 0-199°C, OFF /
32-390°F, OFF
(1°increments)
80
10 DIAG ON
or
DIAG OFF
ALARM ON RTD FAILURE
DIAGNOSTIC
Toggles between
DIAG ON and
DIAG OFF
DIAG ON
Page 3 SP TRIP SETPOINTS FOR TRIP SETTINGS
1 GFT XXX GROUND FAULT TRIP LEVEL
IN % OF GROUND CT RATIO
NUMERATOR
2-55% of Ground
Ct ratio
numerator, OFF
(1% increments)
24%
2 GFSD XX GROUND FAULT START
DELAY IN CYCLES
2-60 ac cycles (1
cycle
increments)
5
3 GFRD XX GROUND FAULT RUN DELAY
IN CYCLES
0-60 ac cycles (1
cycle
increments)
2
4 IOC XXXX INSTANTANEOUS
OVERCURRENT IN % FLA
300-1600%, OFF
(1% increments)
OFF
5 IOCSD XX INSTANTANEOUS
OVERCURRENT START
DELAY IN CYCLES
2-60 ac cycles (1
cycle
increments)
3
6 JMT XXXX JAM TRIP LEVEL IN % FLA 100-1200%, OFF
(1% increments)
1000%
7 JMSD XXX JAM TRIP AND ALARM START
DELAY IN SECONDS
0-1200 sec. (1
sec. increments)
60
8 JMTR XXX JAM TRIP RUN DELAY IN
SECONDS
0-240 sec. (1
sec. increments)
2
9 ULT XXX UNDERLOAD TRIP LEVEL IN
% FLA
6-90%, OFF (1%
increments)
OFF
10 ULSD XXX UNDERLOAD TRIP AND
ALARM START DELAY IN
SECONDS
0-120 sec. (1
sec. increments)
60
11 ULTR XXX UNDERLOAD TRIP RUN
DELAY IN SECONDS
0-240 sec. (1
sec. increments)
10
12 UBT XXX PHASE UNBALANCE TRIP
LEVEL
4-40%, OFF (1%
increments)
OFF
13 UBSD XXX PHASE UNBALANCE TRIP
AND ALARM START DELAY IN
SECONDS
0-120 sec. (1
sec. increments)
10