I.L. 17562
Page 25
PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
14 UBTR XXX PHASE UNBALANCE TRIP
RUN DELAY IN SECONDS
0-240 sec. (1
sec. increments)
2
Page 4 SP ALARM SETPOINTS FOR ALARM SETTINGS
1 GFA XXX GROUND FAULT ALARM
LEVEL IN % OF GROUND CT
RATIO NUMERATOR
2-55% of Ground
Ct ratio
numerator, OFF
(1% increments)
OFF
2 I2TA XXX I2T ALARM LEVEL IN % FULL
OF I2T TRIP CAPACITY
60-99%, OFF
(1% increments)
80
3 JMA XXXX JAM ALARM LEVEL IN % FLA 100-1200%, OFF
(1% increments)
1000%
4 JMAR XXX JAM ALARM RUN DELAY IN
SECONDS
0-240 sec. (1
sec. increments)
2
5 ULA XXX UNDERLOAD ALARM LEVEL
IN % FLA
6-90%, OFF (1%
increments)
OFF
6 ULAR XXX UNDERLOAD ALARM RUN
DELAY IN SECONDS
0-240 sec. (1
sec. increments)
10
7 UBA XXX PHASE UNBALANCE ALARM
LEVEL
4-40%, OFF (1%
increments)
10
8 UBAR XXX PHASE UNBALANCE ALARM
RUN DELAY IN SECONDS
0-240 sec. (1
sec. increments)
10
Page 5 SP START SETPOINTS FOR START SETTINGS
1 ST/T XXX STARTS PER TIME ALLOWED 1-10 starts/time
(increments of 1)
1
2 T/ST XXX TIME ALLOWED FOR
STARTS COUNT IN MINUTES
1-240 minutes,
OFF (1 minute
increments)
OFF
3 TBS XXX TIME BETWEEN STARTS IN
MINUTES
1-240 minutes,
OFF (1 minute
increments)
OFF
4 NOCS X NUMBER OF COLD STARTS
ALLOWED
1-5 starts
(increments of 1)
1
5 TRNC XXX MOTOR START TRANSITION
CURRENT LEVEL IN % FLA
10-300% (1%
increments)
130
6 TRNT XXX MOTOR START TRANSITION
TIME IN SECONDS
0-1200 sec. (1
sec. Increments)
10
7 Choose:
TRN TIME
TRN I
TRN T+C
TRN T/C
TRANSITION ON EVENT
TRN TIME – ON TIME ONLY,
TRN I – ON CURRENT
ONLY,
TRN T+C – ON TIME OR
CURRENT,
TRN T/C – ON TIME AND
CURRENT
Choose one of
the four
conditions that
determine a
start-to-run
transition: TRN
TIME, TRN I,
TRN T+C, or
TRN T/C.
Refer to
setpoints P5L5
and P5L6.
TRN I
8 INSQ XXX INCOMPLETE SEQUENCE
REPORT BACK TIME IN
1-240 sec., OFF
(1 sec.
1