EasyManua.ls Logo

Eaton Cutler-Hammer MP-3000 - Page 26

Eaton Cutler-Hammer MP-3000
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 26 I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
SECONDS ON DISCRETE
INPUT 2
increments)
Note: Choosing
a time value here
(not OFF) also
locks P7L1 to
INC SEQ and no
other choices are
available there.
Also, if this is set
to OFF, later
setting of P7L1
to INC SEQ will
force a setpoint
of 1 second here.
9 INSQ TRN
or
INSQ ST
INCOMPLETE SEQUENCE
START TIMER EVENT
INSQ TRN – START TO RUN
TRANSITION
INSQ ST – STOP TO START
TRANSITION
Toggles between
INSQ TRN and
INSQ ST
INSQ ST
10 LAT XXX LONG ACCELERATION TIME
IN SECONDS
1-1200 sec.,
OFF (1 sec.
increments)
Danger - set to
OFF unless
absolutely
needed. If used,
connect zero-
speed switch -
see P5L11 and
P6L1.
OFF
11 ZSW ON
or
ZSW OFF
ZERO SPEED SWITCH ON
DISCRETE INPUT 1 ON OR
OFF
Toggles between
ZSW ON and
ZSW OFF.
Note: Choosing
ZSW ON here
also locks P6L1
to ZERO SW
and no other
choices are
available there.
Also, setting
P6L1 to ZERO
SW will force
ZSW ON here.
ZSW OFF
12 ABKS XXX ANTI-BACKSPIN DELAY TIME
IN MINUTES
1-240 minutes,
OFF (1 minute
increments)
OFF
Page 6 SP DI 1 SETPOINTS FOR DISCRETE INPUT NUMBER 1
1 Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
EMG OVR
CONFIGURE DISCRETE
INPUT 1 - -
REM RST – REMOTE RESET
REM TRIP – REMOTE TRIP
DIF TRIP – DIFFERENTIAL
TRIP
MTR STOP – MOTOR STOP
Choose from the
seven selections
for the function
of Discrete Input
1.
If ZERO SW is
REM RST

Related product manuals