I.L. 17562
Page 29
PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
PH R OFF RELAY OUTPUT OR DISABLE PH R OFF
16 INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE
SEQUENCE TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
INSQ ON and
INSQ OFF
INSQ OFF
17 REMT
ON
or
REMT
OFF
ENABLE REMOTE TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
REMT ON and
REMT OFF
REMT OFF
18 DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP
TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
DIFT ON and
DIFT OFF
DIFT OFF
19 INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
INCT ON and
INCT OFF
INCT OFF
20 TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP
TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
TRNT ON and
TRNT OFF
TRNT OFF
21 ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED
SWITCH TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR
DISABLE
Toggles between
ZSWT ON and
ZSWT OFF
ZSWT OFF
22 TBYP ON
or
TBYP OFF
ENABLE TRIP BYPASS TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
TBYP ON and
TBYP OFF
TBYP OFF
Page 9 SP AUX1 SETPOINTS FOR AUX 1 RELAY OUTPUT CONFIGURATION
1 LSPU XXX LOAD SHED PICK-UP
CURRENT AS % OF FLA
50-150%, OFF
(1% increments)
Note: P9L1 and
P9L2 are forced
to be coherent.
See Section 5
explanation.
OFF
2 LSDO
XXX
LOAD SHED DROP-OUT
CURRENT AS % OF FLA
50-LSPU Value
%, OFF (1%
increments)
Note: P9L1 and
P9L2 are forced
to be coherent.
See Section 5
explanation.
OFF
3 LSDL XX LOAD SHED DELAY IN
SECONDS
0-5 sec. (0.1 sec.
increments)
1
If LSPU and
LSDO are both
set to OFF then
the SP AUX1
functions below
are available and
visible:
--- ---