Page 28 I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
JAM OFF
4 Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDERLOAD ALARM
OR TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR
DISABLE
Toggles between
UL A ON, UL T
ON, and UL OFF
UL A ON
5 Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
UB A ON, UB T
ON, and UB OFF
UB A ON
6 Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
WD A ON, WD
T ON, and WD
OFF
WD A ON
7 Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
MB A ON, MB T
ON, and
MB OFF
MB A ON
8 Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
LB A ON, LB T
ON, and LB OFF
LB A ON
9 Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD
TEMP ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
AX A ON, AX T
ON, and AX OFF
AX A ON
10 Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME
TRIP OR ALARM TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
SX A ON, SX T
ON, and SX OFF
SX A
11 Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN
STARTS TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR
DISABLE
Toggles between
TBS T ON and
TBS OFF
TBS OFF
12 RTDF
ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD
CHANNEL FAILURE TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
RTDF ON and
RTDF OFF
RTDF ON
13 RCOM ON
or
RCOM
OFF
ENABLE RTD MODULE
COMMUNICATION FAILURE
TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
RCOM ON and
RCOM OFF
RCOM ON
14 IOCT ON
or
IOCT OFF
ENABLE INSTANTANEOUS
TRIP TO ACTIVATE ALARM
RELAY OUTPUT OR DISABLE
Toggles between
IOCT ON and
IOCT OFF
IOCT OFF
15 PH R ON
or
ENABLE PHASE REVERSAL
TRIP TO ACTIVATE ALARM
Toggles between
PH R ON and
PH R OFF

Related product manuals