PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
15 IOC A ON
IOC T ON
or
IOC OFF
ENABLE INSTANTANEOUS
OVERCURRENT ALARM OR
TRIP TO ACTIVATE AUX2
RELAY OUTPUT OR DISABLE
Toggles between
IOCT ON and
IOCT OFF
IOCT OFF
16 PH R ON
Or
PH R OFF
ENABLE PHASE REVERSAL
TRIP TO ACTIVATE AUX2
RELAY OUTPUT OR DISABLE
Toggles between
PH R ON and
PH R OFF
PH R OFF
17 INSQ ON
Or
INSQ OFF
ENABLE INCOMPLETE
SEQUENCE TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
INSQ ON and
INSQ OFF
NSQ OFF
18 REMT ON
Or
REMT OFF
ENABLE REMOTE TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
REMT ON and
REMT OFF
REMT OFF
19 DIFT ON
Or
DIFT OFF
ENABLE DIFFERENTIAL TRIP
TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
DIFT ON and
DIFT OFF
DIFT OFF
20 INCT ON
Or
INCT OFF
ENABLE INCOM TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
INCT ON and
INCT OFF
INCT OFF
21 TRNT ON
Or
TRNT OFF
ENABLE TRANSITION TRIP
TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
TRNT ON and
TRNT OFF
TRNT OFF
22 ZSWT ON
Or
ZSWT OFF
ENABLE ZERO SPEED
SWITCH TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR
DISABLE
Toggles between
ZSWT ON and
ZSWT OFF
ZSWT OFF
23 TBYP ON
Or
TBYP OFF
ENABLE TRIP BYPASS TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
TBYP ON and
TBYP OFF
TBYP OFF
Page 11 SP A OUT SETPOINT FOR ANALOG OUTPUT CONFIGURATION
1
MAX 100
MAX 125
MAX
WRTD
MAX %12T
4-20 MA OUTPUT
MAX 100 – 20 MA FOR 100%
FLA
MAX 125 – 20 MA FOR 125%
FLA
MAX WRTD – 20 MA FOR
TRIP LEVEL
MAX %I2T – 20 MA FOR 100%
I2T
Select one of
MAX 100, MAX
125,
MAX WRTD, or
MAX %I2T
MAX 125
Page 12 SP SYS SETPOINTS FOR SYSTEM CONFIGURATION
1 TP MODE
X
CONFIGURE TRIP RELAY
OUTPUT TO BE MODE 1 –
TRIP RELAY ENERGIZES ON
TRIP EVENT OR MODE 2 –
TRIP RELAY ENERGIZES ON
POWER UP AND DE-
ENERGIZES ON TRIP EVENT
Toggles between
TP MODE1 and
TP MODE2
TP MODE2
2 AL MODE
X
CONFIGURE ALARM RELAY
OUTPUT TO BE MODE 1 –
Toggles between
AL MODE1 and
AL MODE2