I.L. 17562
Page 35
PR 0.3 Effective 8/99
Line
No.
Display Help Message Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
IQ2 DIS IQ2 EN – IQ1000II
EMULATION
IQ2 DIS – MP-3000
COMMUNICATION
DIS
16 RLYF TRP
RLYF ALM
or
RLYF T+A
INTERNAL DIAGNOSTIC
FAILURE ACTIVATES TRIP
AND OR ALARM RELAY
Toggles between
RLYF TRP,
RLYF ALM and
RLYF T+A
RLYF T+A
17 INCT DIS
or
INCT EN
INCOM TRIP DISABLED OR
ENABLED
Toggles between
INCT DIS and
INCT EN
INCT EN
18
DISARMED
or
ARMED
ARM OR DISARM TRIP
RELAY
WARNING DISARM WILL NOT
ALLOW TRIP RELAY TO
FUNCTION
TRIP WARNING MP-3000
WILL BE DISARMED UPON
EXIT OF PROGRAM MODE
AND WILL NOT PROTECT
THE MOTOR-ENTER ARMED
INTO SETPOINT TO
PROTECT THE MOTOR
Toggles between
ARMED and
DISARMED
ARMED
Page 13 SP TEST SETPOINTS FOR TESTING INPUTS AND OUTPUTS
1 3 PHASE
or
1 PHASE
SINGLE PHASE TEST MODE
OR THREE PHASE
PROTECTION MODE
Toggles between
3-PHASE and 1-
PHASE
Note: 1-PHASE
is for bench
testing ONLY.
3-PHASE 3-PHASE
2 TRP ENER
or
TRP DENR
TRP ENER – ENERGIZE TRIP
RELAY
TRP DENR – DE-ENERGIZE
TRIP RELAY
Toggles between
TRP ENER and
TRP DENR
Press and hold
Reset button to
perform selected
test
----- -----
3 ALM ENER
or
ALM DENR
ALM ENER – ENERGIZE
ALARM RELAY
ALM DENR – DE-ENERGIZE
ALARM RELAY
Toggles between
ALM ENER and
ALM DENR
Press and hold
Reset button to
perform selected
test
----- -----
4 AX1 ENER
or
AX1 DENR
AX1 ENER – ENERGIZE
AUXILIARY RELAY 1
AX1 DENR – DE-ENERGIZE
AUXILIARY RELAY 1
Toggle between
AX1 ENER and
AX1 DENR
Press and hold
Reset button to
perform selected
test
----- -----
5 AX2 ENER
or
AX2 DENR
AX2 ENER – ENERGIZE
AUXILIARY RELAY 2
AX2 DENR – DE-ENERGIZE
AUXILIARY RELAY 2
Toggle between
AX2 ENER and
AX2 DENR
Press and hold
----- -----

Related product manuals