PR 0.3 Effective 8/99
Table 4.4 History Mode Display
Note
For any of the Line functions, the Value buttons are used to view the multiple displays.
Page Line Display Complete Help Message Description
HISTORY HISTORY MODE Recalls stored motor data
HIST MTR HISTORY OF MOTOR STATISTICS This page contains historical
information of motor since reset
OCNT XX OCNT XX OPERATION COUNT SINCE LAST
RESET
The number of motor starts logged
since last reset
MM/DD/YY DATE OF RESET The date when OCNT was reset
HH:MM:SS TIME OF RESET The time when OCNT was reset
RT XXXX RT XXXX RUN TIME HOURS SINCE LAST
RESET
Total motor run time accumulated
since last reset
MM/DD/YY DATE OF RESET The date when RT was reset
HH:MM:SS TIME OF RESET The time when RT was reset
IMS XXXX IMS XXXX HIGHEST STARTING PHASE
CURRENT
Highest starting phase current
monitored since last reset
MM/DD/YY DATE OF EVENT The date of highest IMS
HH:MM:SS TIME OF EVENT The time of highest IMS
IMR XXXX IMR XXXX HIGHEST RUNNING PHASE
CURRENT
Highest running phase current
monitored since last reset
MM/DD/YY DATE OF EVENT The date of highest IMR
HH:MM:SS TIME OF EVENT The time of highest IMR
UBM XXX UBM XXX HIGHEST PHASE UNBALANCE Maximum phase unbalance
monitored since last reset
MM/DD/YY DATE OF EVENT Date of highest phase unbalance
HH:MM:SS TIME OF EVENT Time of highest phase unbalance
WMX
XXXX
WMX XXXX HIGHEST MOTOR WINDING
TEMPERATURE IN DEGREES C(F)
Maximum motor winding
temperature monitored since reset
MM/DD/YY DATE OF EVENT The date of highest WMX
HH:MM:SS TIME OF EVENT The time of highest WMX
MBX
XXXX
MBX XXXX HIGHEST MOTOR BEARING
TEMPERATURE IN DEGREES C(F)
Maximum motor bearing
temperature monitored since reset
MM/DD/YY DATE OF EVENT The date of highest MBX
HH:MM:SS TIME OF EVENT The time of highest MBX
LMX
XXXX
LMX XXXX HIGHEST LOAD BEARING
TEMPERATURE IN DEGREES C(F)
Maximum load bearing
temperature monitored since reset
MM/DD/YY DATE OF EVENT The date of highest LMX
HH:MM:SS TIME OF EVENT The time of highest LMX
EMOR
XXX
EMOR XXX NUMBER OF EMERGENCY
OVERRIDES SINCE LAST RESET
Total number of emergency
overrides performed since reset
MM/DD/YY DATE OF RESET The date when EMOR was reset
HH:MM:SS TIME OF RESET The time when EMOR was reset
HIST TRP HISTORY OF TRIP EVENTS This page contains historical
information on trips that have
occurred since reset
GF T XX GF T XX NUMBER OF GROUND FAULT
TRIPS SINCE LAST RESET
Total number of respective trips
that occurred since reset
MM/DD/YY DATE OF RESET The date when respective trip
function was reset
HH:MM:SS TIME OF RESET The time when respective trip
function was reset
I2TT XX I2TT XX NUMBER OF I2T TRIPS SINCE LAST

Related product manuals