Page 66 I.L. 17562
PR 0.3 Effective 8/99
5.13.3 Setpoint P13L3, Alarm Relay Test (ALM ENER or ALM DENR) Lets the user directly
energize or deenergize the alarm relay for testing purposes. Use it in the same way as the trip
relay test. Check the Alarm relay MODE Setpoint P12L2. Unlike the trip output, this output can
be tested with the motor running.
5.13.4 Setpoint P13L4, AUX1 Relay Test (AX1 ENER or AX1 DENR) Lets the user directly
energize or deenergize the AUX1 relay for testing purposes. Use it in the same way as the trip
relay test. Check the AUX1 relay MODE Setpoint P12L3. Unlike the trip output, this output can
be tested with the motor running.
5.13.5 Setpoint P13L5, AUX2 Relay Test (AX2 ENER or AX2 DENR) Lets the user directly
energize or deenergize the AUX2 relay for testing purposes. Use it in the same way as the trip
relay test. Check the AUX2 relay MODE Setpoint P12L4. Unlike the trip output, this output can
be tested with the motor running.
5.13.6 Setpoint P13L6, Force Analog Output Current Value (AOUT 4 , AOUT 12, or
AOUT 20) – To test the analog output, first select the value to force - either 4, 12, or 20 mA..
When ready to test, push and hold the Reset button to observe the forced output value. When
the Reset button is released, the analog output returns to normal operation.
5.13.7 Setpoint P13L7, State of Discrete Input 1 (DI1 ON (or OFF)) Read-only - not a
setting. Use to read if Discrete Input 1 is ON (energized) or OFF.
5.13.8 Setpoint P13L8, State of Discrete Input 2 (DI2 ON (or OFF)) Read-only - not a
setting. Use to read if Discrete Input 2 is ON (energized) or OFF.
5.14 Page 14, SP RESET, Setpoints P14L1 to P14L4 This page is used to reset or clear the
accumulated history mode statistics on each of the four History pages:
Select the History page to clear using the Line pushbuttons.
Push either Value button to get the PUSH RST display.
Press the Reset pushbutton to clear the History page.
To escape without clearing, don't push Reset. Use a Value button to change from PUSH
RST back to [History Page Name] RST, then navigate elsewhere or exit the Program Mode.
The four History pages are:
5.14.1 Setpoint P14L1, Motor History Reset (MTR RST)
5.14.2 Setpoint P14L2, Trip History Reset (TRIP RST)
5.14.3 Setpoint P14L3, Alarm History Reset (ALRM RST)
5.14.4 Setpoint P14L4, History Totals Reset (TOT RST)
See Section 4 for more information on the History Mode displays that can be cleared.