EasyManua.ls Logo

Eaton Digitrip 3000 series - 1-4 STANDARDS; SECTION 2: FUNCTIONAL DESCRIPTION; 2-1 PROTECTION, TESTING AND COMMUNICATION CAPABILITIES; 2-1.1 RMS SENSING

Eaton Digitrip 3000 series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instruction Leaflet DT3000
Page 6 Effective: Date 07/02 I.B. 17555D
For more information visit: www.cutler-hammer.eaton.com
Supersedes I.B. 17555C dated November 1999
Fig. 1-5 Installed Jumpers in Place on Terminal Block
TB-1 Disabling the Zone Interlocking Feature
In addition to being able to provide a circuit breaker
“OPEN” or “CLOSED” status to the remote location, the
Digitrip 3000 displays and remotely transmits parameters,
such as:
Individual phase currents
Ground current
Maximum current for each phase and ground since
last reset (A Demand)
Magnitude and phase of current causing trip
Cause of trip
Current transformer ratio
Existing set point settings
Software Version
The remote communications capability is made possible by
the Cutler-Hammer Integrated Communications (INCOM)
Chip and Protocol which is compatible with the Power-Net
Monitor and Control System. Reliable two-way
communications can be provided over a twisted pair
communications network. The protocol permits a remote
master computer to perform:
1) Interrogation of relay data
2) Execution of circuit breaker “Close” and “Trip”
commands
3) “Reset” of the relay after a trip
4) Downloading of settings
1-4 STANDARDS
Digitrip 3000 Protective Relays are “Component
Recognized” by the Underwriters Laboratory, Inc.® under
UL File E154862. Refer to Section 2-3 UL Testing and
Specification Summary for more information.
SECTION 2: FUNCTIONAL DESCRIPTION
2-1 PROTECTION, TESTING AND COMMUNICATION
CAPABILITIES
2-1.1 RMS SENSING
Digitrip 3000 Protective Relays provide true RMS sensing
for proper correlation with the thermal characteristics of
conductors and equipment. The root-mean-square (rms)
value is determined by a microprocessor calculation of
discrete sampled points of the current waveform. This rms
value is used for the protection response and metering
displays of the relay.
2-1.2 PICKUP SETTING
A Digitrip 3000 Protective Relay pickup setting is a
discrete, pre-selected value of current used to initiate a
tripping action. The Digitrip 3000 has several current
based tripping functions:
Phase inverse time overcurrent tripping - Thermal,
ANSI, and IEC Curves.
Ground inverse time overcurrent tripping - Thermal,
ANSI, and IEC Curves.
Phase and ground short delay tripping.
Phase and ground instantaneous tripping.
AS SHOWN IN FIGURE 3-2, THE ANSI AND IEC
“CURVE SHAPES” ARE IN TERMS OF MULTIPLES OF
I
PU
(PICKUP CURRENT OF THE CT PRIMARY),
WHEREAS ‘SHORT DELAY’ AND “INSTANTANEOUS”
ARE IN TERMS OF MULTIPLES OF I
N
(5A SECONDARY
OF CT PRIMARY CURRENT). THE THERMAL CURVE IS
REPRESENTED IN TERMS OF MULTIPLES OF I
N
FOR
ITS CURVE SHAPE, SHORT DELAY, AND
INSTANTANEOUS SETTINGS. THIS MUST BE
CONSIDERED IN THE COORDINATION STUDY AND IN
THE PROGRAMMING OF THE DIGITRIP 3000
PROTECTIVE RELAY.
EXAMPLE: THERMAL CURVES, SHORT DELAY AND
INSTANTANEOUS SETTINGS USING I
N
Ct Rating = I
n
= 1200A
Pickup Setting = 1.5
Pickup (amperes) = (1 200)(1 .5)
= 1800A
Example: ANSI and lEC curves using I
pu
Ct Rating = 1200A
I
pu
= Pickup Current = 1800A

Table of Contents

Related product manuals