Instruction Leaflet DT3000
Page 36 Effective: Date 07/02 I.B. 17555D
For more information visit: www.cutler-hammer.eaton.com
Supersedes I.B. 17555C dated November 1999
TABLE 6.1 TROUBLESHOOTING GUIDE
Symptom Probable Cause Possible Solution(s) Reference
Protective Relay’s Control
Power is Deficient or
Absent
Verify that Control Power is Connected
Between TB1 -5 and B1 -6 and that it is
within Specifications
Figure 3-1
and
Paragraph 2-
3
Operational LED is
Off
Protective Relay is
Malfunctioning
Replace the Protective Relay Paragraph 6-
3
Protective Relay’s Control
Power is Deficient or
Absent
Verify that Control Power is Connected
Between TBI-5 and TBI-6 and it is within
Specifications
Figure 3-1
and
Paragraph 2-
3
Operational LED is
On but Does not Blink
Protective Relay is
Malfunctioning
Replace the Protective Relay Paragraph 6-
3
Operational LED
Blinks Red
Internal Problem Detected Press Reset Pushbutton
Reprogram Set points
Replace Protective Relay if Symptom
Persists
Paragraph 2-
2.1 and 3-2
Paragraph 3-
3.2
Paragraph 6-
3
Operational LED is
NOT Definite Red or
Green
Internal Problem Detected Press Reset Pushbutton
Reprogram Set points
Replace Protective Relay if Symptom
Persists
Paragraph 2-
2.1 and 3-2
Paragraph 3-
3.2
Paragraph 6-
3
Set points are Invalid Reprogram Set points Paragraph 3-
3.2
“PGRM” Appears in
Settings Display
Window
Check sum did not Match Replace Protective Relay if “PGRM”
Reappears After Saving Settings
Paragraph 6-
3
There was an Error During
Set point Programming
Make Sure DIP switch S2 is in Correct
Position
Table 5.1
“ERR” Appears in
Setting
There was an Error While
in the Test Mode
More than 0.1 Per Unit of Current Cannot
Flow While in Test Mode
Paragraph 3-
3.3
“RAM” Appears in
Settings Display
Window
An Internal RAM Check
Failed
Remove Power from the Protective Relay
and then Reapply Power - If the Symptom
Persists, Replace the Protective Relay
Paragraph 6-
3
Incorrect CT Ratio used in
Equipment
Verify CT Ratio in Equipment Paragraph 1-
3 and
Paragraph 3-
3.2
Incorrect Current Wiring Verify Connections on CT Wiring Figure 3-1
Incorrect System
Frequency Programmed
Set to Correct Frequency Paragraph 3-
3.2
Current Readings
Appear Incorrect
Breaker Contact to trip
unit not functioning
Insure Proper Contact Type is Connected
to Protective Relay and Functioning
Figure 3-1
Incorrect Settings Check Settings Paragraph 3-
3.2 and Table
5.1
Phase Zone Interlocking
not used and Jumper
Missing
Check for Phase Zone Interlocking Jumper
Between TB1 -13 and TB1 -14
Figure 3-1
Circuit Breaker Trips
Much Faster than
Expected on Inverse
Time Overcurrent
Ground Zone Interlocking
not Used and Jumper
Missing
Check for Ground Zone Interlocking
Jumper Between TB1 -11 and TB1 –12
Figure 3-1