Figure 7-7 Instantaneous Curves (SC-5396-92B)
0.01
0.10
1.00
10.00
100.00
1000.00
10000.00
0.1 1 10 100
Multiple of I
n
Value
Trip Time (seconds)
Phase, Lowest Setting Phase, Highest Setting
Ground, Lowest Setting Ground, Highest Setting
Adjustable Instantaneous Trip (Phase Element) (1……….25 x I
n
None)
Adjustable Instantaneous Trip (Ground Element) (0.5……….11 x I
n
None)
Tolerance: Instantaneous Setting is ±10%
Instantaneous uses the Instantaneous Contact