5 Application examples
5.1 Single-channel controlled stop application (cat. 3, SIL 3, PL e) with error prevention
EMS2… Electronic motor starter 10/19 MN034003EN www.eaton.com 35
Figure 19: Single-channel controlled stop application with safety relay with error prevention
(disconnect U
s
)
Motor starter EMS2-ROS… is used in conjunction with an ESR5-series
safety relay. The preset for the control commands for the operating direction
takes place directly at 24 V DC on the L or R terminal. In contrast to the previ-
ous example, in the case of a controlled stop, the supply voltage on the ter-
minals A1 and A2 is switched off by the safety relay.
Please also refer to Page 33 for more information about the lifespan of
devices.
EMS2-ROS-…
Motor starter and safety relay should be located in the same
control panel.