41OPERATION AND INSTALLATION INSTRUCTIONS MN280075EN July 2018
Form 6 microprocessor-based rack-mount recloser control
5 6
3
4
1 2
C
B
A
BYPASS SWITCHES
(CLOSED)
SOURCE SIDE
DISCONNECT SWITCHES
(CLOSED)
LOAD SIDE
DISCONNECT SWITCHES
(OPEN)
CLOSING
COIL
LOAD
SOURCE
SOURCE
LOAD
Figure36. Closing source-side switches of a bypassed on-line recloser provides closing solenoid power for
automatic operation during testing
600:5
Recloser
BCT ON 600:5 Tap
Note: This test circuit
can apply over
800 Amps to the
recloser.
Note: Use at least 2/0
cable between
bushings.
2
1
115Vac
Variable
Autotransformer
(10 Amp)
Clamp-On
Ammeter
Figure37. Alternate method of producing variable line current (substitute for t2 and w-x circuit in Figure38 and
Figure39)