2
For more information see the Room Controller troubleshooting document
www.eaton.com/lightingsystems
Sample Placement Diagram
(For Example Purposes Only)
Wall/Corner Mount
Occupancy Sensor
Room Controller
(Above Entry Door)
Entry
Wallstation
Additional
Wallstation
Daylight
Sensor
Window
General On
Raise
Lower
Whiteboard
Quiet Time
AV Mode
General On
Off
The Room Controller is a room based system that 
simplifies design, code compliance and installation. The 
controller connects to occupancy sensors, daylighting 
sensors, wallstations and receptacle control accessories 
with provided Click & Go QuickConnect cables, providing 
a completely operational, out-of-the-box solution. Control 
up to three switched and three dimmed loads (dependent 
on model ordered) without the need for post-installation 
programming.
Additional advanced integration easily accomodates 
Demand Response, Alert Mode, A/V Mode and Time Clock 
requirements.
This document shows installation details regarding the 
Room Controller and accessory products.
     CAUTION     
Bonding between conduit connections is not automatic and 
must be provided as part of the installation.
Failure to install the Room Controller in the suggested 
location (above the entry door) may lead to the provided 
QuickConnect cabling being too short to reach the intended 
accessory locations.
1
2
3
4
5
6
Integration Controls Adjustable Skylights
Low EndHigh End
Energy
Options
Status
Reset
0-10V Gain
Adjustment
Dimmer 3 Dimmer 2 Dimmer 1
+
--
++
-
0-10V Dimming
0-10V Dimming Outputs
-
+
Dimmer 3 Dimmer 2 Dimmer 1
-
++
-
Blue - EM Line In
Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In
White/Black - 120V N
White/Orange - 277V N
Blue - Load In
Yellow - Load 1 Out
Red - Load 2 Out
Purple - Load 3 Out
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
12 34
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
-
Green
Black
Red
White
Adjustable Skylights
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cables
Sensors
Slider
Station
Wallstations
Room Controller Plastic Enclosure (Model RC3DE shown)
Room Controller Metal Enclosure (Model RC3DE-PL shown)
Specifications
Input/Output Voltage 120/277 VAC 50/60Hz
Maximim Combined Load 20A
 Ballast: 20A (LED)
 Incandescent: 15A
  Motor Load: 1 HP @ 120 VAC
Emergency Output: (RC3DE only)
 Ballast: 3A (LED)
 Incandescent: 3A
Class 2 Dimming Output 0-10 VDC, sinks up to 100mA 
per output for control of up to 50 
compatible ballasts/drivers.
Operating Environment 32° F to 104° F (0° to 40° C) 
For indoor use only.