Table 5-1. Quik-Start Set-Up for Basic Regulation
Function Code Description Instructions
Security
099 Security Function, 99, Enter, Password (32123), Enter
Forward Settings
001 Forward Set Voltage Function, 1, Enter, Edit, Value, Enter
002 Forward Bandwidth Function, 2, Enter, Edit, Value, Enter
003 Forward Time Delay Function, 3, Enter, Edit, Value, Enter
004 Forward Line Drip Comp. Resistance Function, 4, Enter, Edit, Value, Enter
005 Forward Line Drip Comp. Reactance Function, 5, Enter, Edit, Value, Enter
Reverse Settings
056 Reverse Sensing Mode Function, 56, Enter, Scroll - Locked Forward; Locked Reverse; Reverse Idle;
Bi-Directional; Neutral Idle; Co-generation; React Bi-directional, Enter
039 Source Voltage Calculation Function, 39, Enter, Edit, Scroll - On or Off, Enter
140 Regulator Type Function, 140, Enter, Edit, Scroll - Type A; Type B; Type C; Type D, Enter
051 Reverse Set Voltage Function, 51, Enter, Edit, Value, Enter
052 Reverse Bandwidth Function, 52, Enter, Edit, Value, Enter
053 Reverse Time Delay Function, 53, Enter, Edit, Value, Enter
054 Reverse Line Drip Comp. Resistance Function, 54, Enter, Edit, Value, Enter
055 Reverse Line Drip Comp. Reactance Function, 55, Enter, Edit, Value, Enter
Configurations
041 Regulator Configuration Function, 41, Enter, Edit, Scroll - Wye; Delta Lag; Delta Lead, Enter
042 Control Operation Mode Function, 42, Enter, Edit, Scroll - Sequential; Time-Integrating; Voltage-
Averaging, Enter
043 System Line Voltage Function, 43, Enter, Edit, Value, Enter
044 Overall P.T. Ratio Function, 44, Enter, Edit, Value, Enter
045 C.T. Primary Rating Function, 45, Enter, Edit, Value, Enter
049 Tap-Changer Type Function, 49, Enter, Edit, Scroll - Cooper QD8; Cooper QD5; Cooper QD3;
Cooper Spring Drive; Cooper Direct Drive; Siemens; General Electric;
Howard; LTC-Reinhausen, Enter
050 System Calendar and Clock Function, 50, Enter, Edit, Month, Day, Year, Hour, Minute, Enter
069 Auto Operation Blocking Status Function, 69, Enter, Edit, Scroll - Normal; Blocked, Enter
Voltage Reduction
070 Voltage Reduction Mode Function, 70, Enter, Edit, Scroll - Off; Local/Digital Remote; Remote/Latch,
Remote/Pulse, Enter
072 Local/Digital Reduction Value Function, 72, Enter, Edit, Value, Enter
073 Remote #1 Value Function, 73, Enter, Edit, Value, Enter
074 Remote #2 Value Function, 74, Enter, Edit, Value, Enter
075 Remote #3 Value Function, 75, Enter, Edit, Value, Enter
076 # of Pulse Reduction Steps Function, 76, Enter, Edit, Value, Enter
077 % of Voltage Red Per Pulse Step Function, 77, Enter, Edit, Value, Enter
Voltage Limiter
080 Voltage Limiter Mode Function, 80, Enter, Edit, Scroll - Off; High Limit Only; High/Low Limit, Enter
081 High Voltage Limit Function, 81, Enter, Edit, Value, Enter
082 Low Voltage Limit Function, 82, Enter, Edit, Value, Enter
29
CL-6 SERIES CONTROL INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225016EN January 2016

Table of Contents

Other manuals for Eaton GridAdvisor Series II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton GridAdvisor Series II and is the answer not in the manual?

Eaton GridAdvisor Series II Specifications

General IconGeneral
BrandEaton
ModelGridAdvisor Series II
CategoryCables and connectors
LanguageEnglish

Related product manuals