5
Instructional Leaet IL019116EN
Effective July 2016
Installation guidelines for users of Magnum DS
Low-Voltage Front-Access Switchgear Assemblies
for seismic applications
EATON www.eaton.com
a
c
c
Detail A
Front compartment
seismic brace
(shipped installed
at the ends of the
line-up only!)
Seismic wallmount brace
(shipped installed on gear)
Detail B
A
B
1/2-inch tie-down
hardware
1/2-inch tie-down
hardware
1/2-inch tie-down
hardware
a
b
Figure 4. Magnum switchgear front-access rear frame seismic wall brace and front compartment seismic brace information
a
Secure enclosure to pad and/or wall with Grade 5 hardware.
b
Front compartment must be secured to pad for both rear frame wallmount and rear frame floormount applications.
c
A distance of 2.00 inches (50.8 mm), between the wall and the rear of the switchgear, is required to properly secure Front-Access Switchgear when using the rear wallmount brace.