Technical Data
Effective: May 1998Page 36
TD.44A.01.T.E
Cutler-Hammer
Magnum DS
Metal-Enclosed
Low-Voltage Switchgear
Features – Instrumentation/
Metering
Flexibility — Magnum DS Switchgear
allows for a variety of metering
options:
Analog switchboard type meters
such as ammeters, voltmeters, watt-
hour, power factor, etc.
Electronic power metering such as
the IQ family of Analyzer, DP-4000,
etc.
Instrument door mounted meters.
For feeder circuit instrumentation,
2% accuracy ammeters and amme-
ter switches can be mounted on the
secondary contact compartment
door between the breaker compart-
ment doors. The ammeters and
switches are immediately associ-
ated with definite breaker circuits.
Other devices, such as control push-
buttons, breaker control switches,
indicating lights, and test switches
can be mounted on these panels,
within space limitations.
Voltage Transformers — Voltage
transformers are rated 10 kV BIL and
are protected by both primary and sec-
ondary fuses. The primary fuses are of
the current limiting type.
Current Transformers — Current
Transformers for metering and instru-
mentation are mounted in the breaker
compartments and are front accessi-
ble. Secondary wiring between the cur-
rent transformer and the standard
shorting terminal block is color-coded
for ease of identification.
Control Power Transformers — Con-
trol transformers are provided when
required for ac control of circuit break-
ers, space heaters, and/or transformer
fans. Like voltage transformers, they
are protected by current limiting pri-
mary fuses. Non-current limiting fuses
are used on the secondary side to pro-
tect branch circuits.
Instrumentation – Door Mounted
Secondary Terminal Compartment
Door — Devices, such as control push-
buttons, breaker control switches, indi-
cating lights, and test switches can be
mounted on these panels, within space
limitations. The ammeters and
switches are immediately associated
with definite breaker circuits.
Instrument Compartment Door
Devices, such as electronic power
metering and analog switchboard type
meters that do not fit on the secondary
terminal compartment door, are
Features – Accessories
and Options
Switchgear Accessories — Standard
accessories furnished with each Mag-
num DS Switchgear assembly include:
One breaker levering crank
Insulating covers or “boots” are fur-
nished on live main stationary dis-
connecting contacts in compart-
ments equipped for future breakers
Removable cover to block opening
in the door when the breaker is tem-
porarily removed from its compart-
ment
Optional Accessories
Traveling type circuit breaker lifter,
rail-mounted on top of switchgear
Floor running portable circuit
breaker lifter and transfer truck with
manual lifting mechanism. This
requires approximate 84-inch
(2134 mm) deep front aisle space
Test cabinet for electrically operated
breakers, with pushbuttons, control
cable and receptacle, for separate
mounting
Portable test kit for secondary injec-
tion testing and verification of trip
units. Utilizes standard 120 volt, 15
ampere, single-phase, 60 Hz supply,
available from any outlet
Additional removable cover to
block opening in the door when
breaker is temporarily removed
from its compartment
Removable insulating boots over
power cable lug adapters
Optional Switchgear Mounted Lifter
mounted on the Instrument compart-
ment door or on a the panel of a blank
cell.
Devices Mounted on Secondary Terminal
Compartment Door
Devices Mounted on Instrument
Compartment Door