Technical Data
Effective: May 1998 Page 23
TD.44A.01.T.E
Cutler-Hammer
Magnum DS
Metal-Enclosed
Low-Voltage Switchgear
Application
Application of Magnum DS Power Circuit Breakers
With Standard Three-Phase Transformers – Fluid Filled and Ventilated Dry Types
Transformer Base
(100%) Rating
Secondary Short-Circuit Currents
RMS Symmetrical Amperes
Minimum Size Breakers for Selective
Trip Systems
kVA and
Percent
Impedance
Amperes Maximum Short Circuit
kVA Available from
Primary System
Through
Transformer
Only
Motor
Contribution
Combined Main
Breaker
Short Delay
Trip
Feeder
Breaker
Short Delay
Trip
Feeder
Breaker
Instantaneous
Trip
Table A1 – 208 Volts Three-Phase — 50% Motor Load
300
5.0%
833 50000
100000
150000
250000
500000
Unlimited
14900
15700
16000
16300
16500
16700
1700 16600
17400
17700
18000
18200
18400
MDS-616 MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
500
5.0%
1389 50000
100000
150000
250000
500000
Unlimited
23100
25200
26000
26700
27200
27800
2800 25900
28000
28800
29500
30000
30600
MDS-616
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
750
5.75%
2083 50000
100000
150000
250000
500000
Unlimited
28700
32000
33300
34400
35200
36200
4200 32900
36200
37500
38600
39400
40400
MDS-632 MDS-408
MDS-408
MDS-408
MDS-608
MDS-608
MDS-608
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
1000
5.75%
2778 50000
100000
150000
250000
500000
Unlimited
35900
41200
43300
45200
46700
48300
5600 41500
46800
48900
50800
52300
53900
MDS-632
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
Table A2 – 240 Volts Three-Phase — 100% Motor Load
300
5.0%
722 50000
100000
150000
250000
500000
Unlimited
12900
13600
13900
14100
14300
14400
2900 15800
16500
16800
17000
17200
17300
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
500
5.0%
1203 50000
100000
150000
250000
500000
Unlimited
20000
21900
22500
23100
23600
24100
4800 24800
26700
27300
27900
28400
28900
MDS-616
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-08
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
750
5.75%
1804 50000
100000
150000
250000
500000
Unlimited
24900
27800
28900
29800
30600
31400
7200 32100
35000
36100
37000
37800
38600
MDS-620
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
1000
5.75%
2406 50000
100000
150000
250000
500000
Unlimited
31000
35600
37500
39100
40400
41800
9600 40600
45200
47100
48700
50000
51400
MDS-632
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
At transformer self-cooled rating.
Next larger frame size main breaker may be
required for 55/65°C rise and/or forced air-
cooled (FA) transformer. Check Transformer
Secondary Ampere Rating.