Technical Data
Effective: May 1998Page 24
TD.44A.01.T.E
Cutler-Hammer
Magnum DS
Metal-Enclosed
Low-Voltage Switchgear
Application
Application of Magnum DS Power Circuit Breakers
With Standard Three-Phase Transformers – Fluid Filled and Ventilated Dry Types,
Continued
Transformer Base
(100%) Rating
Secondary Short-Circuit Currents
RMS Symmetrical Amperes
Minimum Size Breakers for Selective
Trip Systems
kVA and
Percent
Impedance
Amperes Maximum Short Circuit
kVA Available from
Primary System
Through
Transformer
Only
Motor
Contribution
Combined Main
Breaker
Short Delay
Trip
Feeder
Breaker
Short Delay
Trip
Feeder
Breaker
Instantaneous
Trip
Table A3 – 480 Volts Three-Phase — 100% Motor Load
500
5-0%
601 50000
100000
150000
250000
500000
Unlimited
10000
10900
11300
11600
11800
12000
2400 12400
13300
13700
14000
14200
14400
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
750
5.75%
902 50000
100000
150000
250000
500000
Unlimited
12400
13900
14400
14900
15300
15700
3600 16000
17500
18000
18500
18900
19300
MDS-616 MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
1000
5.75%
1203 50000
100000
150000
250000
500000
Unlimited
15500
17800
18700
19600
20200
20900
4800 20300
22600
23500
24400
25000
25700
MDS-616
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
1500
5.75%
1804 50000
100000
150000
250000
500000
Unlimited
20600
24900
26700
28400
29800
31400
7200 27800
32100
33900
35600
37000
38600
MDS-620
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
2000
5.75%
2406 50000
100000
150000
250000
500000
Unlimited
24700
31000
34000
36700
39100
41800
9600 34300
40600
43600
46300
48700
51400
MDS-632
MDS-408
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-408
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
2500
5.75%
3008 50000
100000
150000
250000
500000
Unlimited
28000
36500
40500
44600
48100
52300
12000 40000
48500
52500
56600
60100
64300
MDS-632
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
3000
5.75%
3609 50000
100000
150000
250000
500000
Unlimited
30700
41200
46600
51900
56800
62800
14000 44700
55200
60600
65900
70800
76800
MDS-840
MDS-608
MDS-608
MDS-608
MDS-808
MDS-808
MDS-808
MDS-608
MDS-608
MDS-608
MDS-808
MDS-808
MDS-808
3750
5.75%
4511 50000
100000
150000
250000
500000
Unlimited
34000
47500
54700
62200
69400
78500
18000 52000
65500
72700
80200
87400
96500
MDS-850 MDS-608
MDS-808
MDS-808
MDS-808
MDS-L08
MDS-L08
MDS-608
MDS-808
MDS-808
MDS-808
MDS-C08
MDS-C08
At transformer self-cooled rating.
Next larger frame size main breaker may be
required for 55/65°C rise and/or forced air-
cooled (FA) transformer. Check Transformer
Secondary Ampere Rating.