Technical Data
Effective: May 1998 Page 25
TD.44A.01.T.E
Cutler-Hammer
Magnum DS
Metal-Enclosed
Low-Voltage Switchgear
Application
Application of Magnum DS Power Circuit Breakers
With Standard Three-Phase Transformers – Fluid Filled and Ventilated Dry Types,
Continued
Transformer Base
(100%) Rating
Secondary Short-Circuit Currents
RMS Symmetrical Amperes
Minimum Size Breakers for Selective
Trip Systems
kVA and
Percent
Impedance
Amperes Maximum Short Circuit
kVA Available from
Primary System
Through
Transformer
Only
Motor
Contribution
Combined Main
Breaker
Short Delay
Trip
Feeder
Breaker
Short Delay
Trip
Feeder
Breaker
Instantaneous
Trip
Table A4 – 600 Volts Three-Phase — 100% Motor Load
500
5.0%
481 50000
100000
150000
250000
500000
Unlimited
8000
8700
9000
9300
9400
9600
1900 9900
10600
10900
11200
11300
11500
MDS-408 MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
750
5.75%
722 50000
100000
150000
250000
500000
Unlimited
10000
11100
11600
11900
12200
12600
2900 12900
14000
14500
14800
15100
15500
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
1000
5.75%
962 50000
100000
150000
250000
500000
Unlimited
12400
14300
15000
15600
16200
16700
3900 16300
18200
18900
19500
20100
20600
MDS-616 MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
1500
5.75%
1443 50000
100000
150000
250000
500000
Unlimited
16500
20000
21400
22700
23900
25100
5800 22300
25800
27200
28500
29700
30900
MDS-616
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
2000
5.75%
1924 50000
100000
150000
250000
500000
Unlimited
19700
24800
27200
29400
31300
33500
7700 27400
32500
34900
37100
39000
41200
MDS-620
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
MDS-408
2500
5.75%
2406 50000
100000
150000
250000
500000
Unlimited
22400
29200
32400
35600
38500
41800
9600 32000
38800
42000
45200
48100
51400
MDS-632
MDS-408
MDS-408
MDS-408
MDS-608
MDS-608
MDS-608
MDS-408
MDS-408
MDS-408
MDS-608
MDS-608
MDS-608
3000
5.75%
2886 50000
100000
150000
250000
500000
Unlimited
24600
33000
37300
41500
45500
50200
11500 36100
44500
48800
53000
57000
61700
MDS-632
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
MDS-408
MDS-608
MDS-608
MDS-608
MDS-608
MDS-608
3750
5.75%
3608 50000
100000
150000
250000
500000
Unlimited
27200
38000
43700
49800
55500
62800
14400 41600
52400
58100
64200
69900
77200
MDS-840
MDS-408
MDS-608
MDS-608
MDS-608
MDS-808
MDS-808
MDS-408
MDS-608
MDS-608
MDS-608
MDS-808
MDS-808
At transformer self-cooled rating.
Next larger frame size main breaker may be
required for 55/65°C rise and/or forced air-
cooled (FA) transformer. Check Transformer
Secondary Ampere Rating.
www . ElectricalPartManuals . com