Instruction Manual Pow-R-Line Retrofit Panelboards
Page 12 Effective: November 2007
P1R & P2R Retrofit Panels
For more information visit: www.EatonCanada.ca
11/2007
Water Damage
DO NOT WORK ON SURFACES OR FLOORS
WHERE THERE IS STANDING WATER.
DO NOT WORK ON WET ENERGIZED
ELECTRICAL
EQUIPMENT.
Major accumulation of water or moisture on any
part of the panelboard can cause catastrophic
damage to the panelboard. If a panelboard has
been submerged by more than 2 inches or where
running or standing water has had contact with
current carrying parts, it has sustained significant
damage.
The panelboard and its components may be
damaged beyond repair and may need replacement.
1. Do not attempt to clean or repair
water-damaged equipment or
components.
2. De-energize the panelboard at its
source.
3. Do not energize.
4. Contact Eaton Electrical for
replacement.
Minor accumulations of moisture, such as
condensation, over a short period of time may be
corrected using heat. De-energize panelboard.
Apply approximately 250 watts per vertical section
for a sufficient period of time until the moisture
disappears, then remove all heat sources and
materials used for drying. Inspect for damage to
components and any corrosion. If any damage or
corrosion is present, contact Eaton Electrical. DO
NOT RE-ENERGIZE PANELBOARD. After the
panelboard has completely dried, remove all
materials and tools from the equipment. Inspect all
connections for damage and torque. Re-install all
covers, fillers, dead-front assemblies and side
sheets. Conduct panelboard insulation resistance
testing described in this publication.
Renewal Parts
To ensure safety and to maintain UL
TM
listing and
CSA
TM
approval, it is essential that only new parts
and components from Eaton Electrical be utilized.
When ordering renewal parts or when requesting
information on the panelboard, it is essential to
include as much information as possible.
Each panelboard will have a nameplate and other
identification marks with details that will help
expedite information requests and orders. The
following may be required to help identify parts and
information requests.
___ Catalog number of the panelboard
___ Description of the equipment
___ Supply voltage
___ Equipment ratings
___ Description of the part
___ Style number of part, if available
___ Rating of part(s)
Electrical distribution equipment has a limited life
span. As such, the manufacturer cannot guarantee
the availability of obsolete equipment or parts.
Equipment replacement may be recommended.
WET PANELBOARDS PRESENT A HAZARDOUS
CONDITION AND MAY CAUSE INJURY OR
DEATH. DE-ENERGIZE POWER TO ALL
EQUIPMENT BEFORE SERVICING.
DO NOT WORK ON PANELBOARDS OR ENTER
AREAS THAT HAVE STANDING WATER. DE-
ENERGIZE ALL EQUIPMENT IN AREAS WITH
STANDING WATER.
PANELBOARD COMPONENTS, INCLUDING
CIRCUIT BREAKERS, FUSIBLE SWITCHES,
METERING, ETC., SUBJECTED TO WATER OR
MOISTURE MAY BE RENDERED UNSAFE.
REPLACEMENT IS REQUIRED.
IL01417001E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Pow-R-Line P2R Series and is the answer not in the manual?

Eaton Pow-R-Line P2R Series Specifications

General IconGeneral
BrandEaton
ModelPow-R-Line P2R Series
CategoryPower distribution unit
LanguageEnglish

Related product manuals