23
7 Event, alarm, and trip recording with waveform capture
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN June 2018 www.eaton.com
7.1 Trigger and data log matrix
What data is captured:
Event cause
Time-stamp
Current: IA, IB, IC, IN, IG
Voltages: VAB, VBC, VCA, VAN, VBN, VCN (PXR 25 only)
Power and demand: watts, Vars, VA (PXR 25 only)
Power factor (PXR 25 only)
Line frequency
Breaker operations count
Trip unit internal temperature
What triggers a capture:
Waveform of: IA, IB, IC, IN, IG
Waveform of: VAB, VBC, VCA, VAN, VBN, VCN
(PXR25)
Event - power up - clock ok
Event - power up - clock bad
Event - set points download
Event - Enter test mode
Event - exit test mode
Event - test complete
Event - enter maintenance mode
Indicator also illuminates
Event - exit maintenance mode
Event - time change (if > 60 seconds)
Previous time is recorded
Alarm - calibration
Alarm - set points fault
Alarm - battery low voltage
Alarm - low control voltage
Alarm - RTC error
Alarm - NV memory error
Alarm - watchdog timer
Alarm - long delay pickup (test mode)
Alarm - ground fault (test mode)
Alarm - trip actuator fault
Alarm - operations count
Alarm - long delay pickup
Alarm - ground fault
Alarm - high load
Alarm - neutral current
Trip - over temperature
Trip - test
Trip - long delay
All trips include four cycles before trip and six
cycles after cycles of waveform capture
Trip - short delay
Trip - instantaneous
Trip - ground
Trip - maintenance mode
Trip - neutral